The AVC63-12B2 Diesel Single-Phase Brushless Generator AVR is suitable for use with Basler generators
DC power output
AVC63-12: large continuous output 12Adc@63Vdc, 10 seconds strong excitation output 24Adc@125Vdc, excitation winding I small resistance value of 5.25 ohms.
AVC125-10: large continuous output 10Adc@125Vdc, 10 seconds strong excitation output 20Adc@250Vdc, excitation winding, small resistance value 12.5 ohms.
AC input power:
Single-phase or three-phase, 50~400Hz.
AVC63-12: 90~153Vac, large continuous power consumption 1092VA.
AVC125-10: 180~264Vac, large continuous power consumption 1750VA.
Detection of Input Voltage and Frequency:
Single-phase or three-phase. Detection voltage option A: 90~139Vac, detection voltage option B: 80~264Vac.
Detection Frequency Option 1: Rated 50/60Hz, Detection Frequency Option 2: Rated 400Hz.
Auxiliary Inputs:
±3Vde, adaptable to SCP250 reactive power/power factor controller or EL200 large/small excitation limiter.
External voltage adjustment potentiometer: 10 thousand ohms, 2 watt potentiometer.